Tripp Lite SU1000RTXLCD2U SmartOnline Series Rack Mount UPS System

 

Have a Question? Call Toll Free: 888-462-7828

Live Chat Email Us
Dale #:TRIP-SU1000RTXLCD2U

Availability: Usually ships in 5 - 10 Days

This item usually ships within 5-10 days after your order is placed. Your payment will be charged after completing checkout.
Free Shipping (Continental US)
  • Tripp Lite Smart Online UPS systems offer high performance power protection ideal for critical server and network equipment in datacenters, computer rooms and network closets. Online, double-conversion Uninterruptible Power Supply (UPS) maintains perfectly regulated output power by continuously converting raw AC input to DC, then re-converting output back to AC. Fully regulated sine wave AC output with +/-2% voltage regulation powers network equipment continuously, even during severe brownouts and overvoltages, all without depleting UPS battery reserves. Maintains battery-derived AC output during power failures with zero transfer time. Extended runtime options available.

    Features:

    • Tripp Lite SU1000RTXLCD2U 1000VA / 1kVA / 900W on-line, double-conversion 2U rack / tower UPS
    • Selectable 100/110/120/127V output (120V factory preset)
    • NEMA 5-15P input, 6 NEMA 5-15R outlets
    • Two switched outlets support remote reboot or programmable load shedding options
    • Supports 2% output voltage regulation and zero transfer time in double conversion mode
    • Economy mode option offers enhanced efficiency, reduced power consumption and lower BTU emissions
    • 14 minutes runtime at 50% load (450W) and 4.8 minutes at 100% load (900W) with internal batteries
    • BP24V15RT2U (limit 1), BP24V28-2U (limit 1), BP24V70-3U (multi-pack compatible) and BP24V36-2US (multi-pack compatible) external battery packs available (some configurations require Tripp Lite's External Battery Configuration Software)
    • LCD interface reports operating mode plus 9 selectable screens of UPS data (Load % & kW, Load % & kVA, Power factor, Input volts & Hz, Output volts & Hz, Battery volts and charge %, Minutes runtime, Capacity remaining, Kw/hr. consumption)
    • LCD interface also supports 16 screens of UPS configuration and setup options
    • 4 post installation hardware included, Optional 2POSTRMKITWM enables 2 post rack / wallmount installation, Optional 2-9USTAND enables tower placement
    • Single line TEL / Network surge suppression
    • Electronic bypass maintains utility output during a variety of UPS fault conditions
    • Battery independent restart ensures automatic UPS power-up without user interaction after lengthy power outages, even when batteries are expired and require replacement
    • Frequency regulation / conversion mode offers generator-compatible frequency correction or conversion of frequency from 50 to 60Hz or 60 to 50Hz
    • Built-in USB, RS-232, contact-closure and optional SNMPWEBCARD accessory monitoring options
    • HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X
    • Included PowerAlert UPS monitoring software

    Interactive LCD interface reports UPS operating mode, detailed UPS and site-power data, plus enables a variety of UPS setup and configuration options. Highly efficient operation in optional economy mode saves BTU heat output and energy costs. Network management interfaces support communications via USB, RS-232, contact-closure and optional SNMPWEBCARD network interface. Built-in DB9 port offers both enhanced RS-232 data and basic contact closure monitoring ability. HID-compliant USB interface enables integration with built-in power management and auto shutdown features of Windows and Mac OS X. Includes PowerAlert monitoring software and complete cabling. Emergency Power Off (EPO) interface. LED display reports UPS operating mode, line power availability, battery mode operation, inverter operation, ECO mode status and output power availability. LED/LCD display panel easily rotates for viewing in rackmount or tower configurations. Audible alarm with push-button momentary alarm-cancel and silent-mode LCD configuration options. Programmable self-test. Fault-tolerant auto-bypass mode. Battery independent restart. Field-replaceable, hot-swappable internal batteries and external battery packs.

  • OUTPUT  
    Output Capacity Details ON LINE MODE: Maximum output capacity ratings are reduced for some nominal voltage settings (127/120/115/110V 900 watts, 100V 810 watts). FREQUENCY REGULATION / CONVERSION MODE: Maximum output ratings are reduced in frequency regulation / conversion mode (127/120/115/110V 630 watts / 100V 567 watts).
    Output Volt Amp Capacity (VA) 1000
    Output kVA Capacity (kVA) 1
    Output Watt Capacity (Watts) 900
    Power Factor 0.9
    Crest Factor 3:1
    Nominal Output Voltage(s) Supported 100V; 110V; 115V; 120V; 127V
    Nominal Voltage Details 120V factory-default nominal voltage
    Frequency Compatibility 50 / 60 Hz; Supports 50 to 60 Hz and 60 to 50 Hz conversion
    Frequency Compatibility Details ON LINE MODE: Output frequency is automatically configured to match nominal input frequency on startup; Output matches input frequency when +/-5Hz of nominal; Output is regulated to +/-0.05Hz when input frequency exceeds +/-5Hz of nominal. UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. FREQUENCY REGULATION / CONVERSION MODE: Output is regulated to +/-0.05Hz of selected output frequency input is 40 to 70Hz; UPS switches to battery mode when input frequency is below 40Hz or above 70Hz. BATTERY MODE: Output is regulated to +/-0.05Hz.
    Output Voltage Regulation (Line Mode) +/- 2%
    Output Voltage Regulation (Economy Line Mode) +/- 10%
    Output Voltage Regulation (Battery Mode) +/- 3%
    Output Receptacles (6) 5-15R
    Load Management Receptacles Two switchable single-outlet 5-15R load banks
    Output AC Waveform (AC Mode) Pure Sine wave
    Output AC Waveform (Battery Mode) Pure Sine wave
    INPUT  
    Rated input current (Maximum Load) 8.6A
    Nominal Input Voltage(s) Supported 100V AC; 110V AC; 115V AC; 120V AC; 127V AC
    Nominal Input Voltage Description 120V factory default
    UPS Input Connection Type 5-15P
    Input Circuit Breakers 15A
    UPS Input Cord Length (ft.) 10
    UPS Input Cord Length (m) 3
    Recommended Electrical Service 15A 120V
    Input Phase Single-Phase
    BATTERY  
    Full Load Runtime (min.) 4.8 min. (900w)
    Half Load Runtime (min.) 14 min. (450w)
    Expandable Battery Runtime Extended runtime supported via optional external battery packs
    External Battery Pack Compatibility BP24V15RT2U (limit 1); BP24V28-2U (limit 1); BP24V70-3U (multi-pack compatible); BP24V36-2US (multi-pack compatible)
    Expandable Runtime Description Some external battery configurations require the use of Tripp Lite's External Battery Configuration Software, see manual for details
    DC System Voltage (VDC) 24
    Battery Recharge Rate (Included Batteries) Less than 3 hours recharge to 90% (typical, full load discharge)
    Internal UPS Replacement Battery Cartridge RBC24V-LCD
    Battery Access Front panel battery access
    Battery Replacement Description Hot-swappable, user replaceable batteries
    VOLTAGE REGULATION  
    Voltage Regulation Description Online, double-conversion power conditioning maintains 2% output voltage regulation during brownouts and overvoltages
    Overvoltage Correction Corrects overvoltages to 150V (0-100% load)
    Undervoltage Correction Corrects undervoltages to 100V at full load (90V at 100V nominal)
    Severe Undervoltage Correction Corrects brownouts to 70V (70% load) & 55V (33% load)
    LEDS ALARMS & SWITCHES  
    LED Indicators 7 front panel LEDs indicate line power availability, AC to DC conversion, battery mode operation, inverter mode, eco mode operation, bypass mode operation and AC output status
    Front Panel LCD Display Front panel LCD information and configuration screen offers detailed UPS and site power status and operating data, plus configuration of voltage, frequency, operating mode, alarm function and a variety of additional options
    Audible Alarm Audible alarm indicates UPS startup, power-failure, low-battery, overload, UPS fault and remote shutdown conditions
    Alarm Cancel Operation Power-fail alarm can be temporarily silenced using alarm-cancel switch; silent mode alarm configuration option available
    Switches 2 switches control off/on power status and alarm-cancel operation; 2 additional scroll-down and scroll-up / select options enable LCD status viewing and configuration options
    SURGE / NOISE SUPPRESSION  
    UPS AC Suppression Joule Rating 570
    UPS AC Suppression Response Time Instantaneous
    UPS Dataline Suppression 1 line TEL/DSL (1 in / 1 out); 10/100Base T Ethernet
    EMI / RFI AC Noise Suppression Yes
    PHYSICAL  
    Included Mounting Accessory Description Adjustable 4 post rack rails included
    Installation Form Factors Supported with Optional Accessories 2 post rackmount (2POSTRMKITWM); Wallmount (2POSTRMKITWM); Tower (2-9USTAND)
    Primary Form Factor Rackmount
    UPS Power Module Dimensions (hwd, in.) 3.5 x 17.5 x 12.5
    UPS Power Module Dimensions (hwd, cm) 8.9 x 44.4 x 31.8
    Rack Height (U Spaces) 2U
    UPS Power Module Weight (lbs.) 29
    UPS Power Module Weight (kg) 13.2
    UPS Shipping Dimensions (hwd / in.) 9.5 x 20 x 24
    UPS Shipping Dimensions (hwd / cm) 24.1 x 50.8 x 61
    Shipping Weight (lbs.) 41.5
    Shipping Weight (kg) 18.8
    Cooling Method Fan
    UPS Housing Material Steel
    ENVIRONMENTAL  
    Operating Temperature Range +32 to +104 degrees Fahrenheit / 0 to +40 degrees Celsius
    Storage Temperature Range +5 to +122 degrees Fahrenheit / -15 to +50 degrees Celsius
    Relative Humidity 0 to 95%, non-condensing
    AC Mode BTU / Hr. (Full Load) 341
    AC Economy Mode BTU / Hr. (Full Load) 230
    Battery Mode BTU / Hr. (Full Load) 585
    AC Economy Mode Efficiency Rating (100% Load) 93%
    Operating Elevation (ft.) 0-3000m / 0-10,000 ft.
    Audible Noise 45 dBA at 1m front side
    COMMUNICATIONS  
    Communications Interface USB (HID enabled); DB9 Serial; Contact closure; EPO (emergency power off); Slot for SNMP/Web interface
    Network Monitoring Port Description Supports detailed monitoring of UPS and site power conditions; DB9 port supports RS232 and contact closure communications
    PowerAlert Software Included
    Communications Cable USB and DB9 cabling included
    WatchDog Compatibility Supports Watchdog application, OS and hard-reboot restart options for remote applications
    LINE / BATTERY TRANSFER  
    Transfer Time Zero (0 milliseconds) in double-conversion mode; 4 milliseconds economy mode
    Low Voltage Transfer to Battery Power (Setpoint) 100V at full load (90V full load at 100V nominal setting); 70V at 70% load; 55V at 33% load
    High Voltage Transfer to Battery Power (Setpoint) 150
    SPECIAL FEATURES  
    Cold Start (Startup in Battery Mode During a Power Failure) Cold-start operation supported
    High Availability UPS Features Automatic inverter bypass; Hot swappable batteries
    Green Energy-Saving Features High efficiency economy mode operation; Individually controllable load banks; Schedulable daily hours of economy mode operation
    CERTIFICATIONS  
    UPS Certifications Tested to UL1778 (USA); Tested to CSA (Canada); Meets FCC Part 15 Category B (EMI); ROHS (Restriction of Hazardous Substances); ENERGY STAR Qualified
    WARRANTY  
    Product Warranty Period (Worldwide) 2-year limited warranty
  • Shipping rates calculator